Process analytical instruments, also known as online analytical instruments, are a general term for instruments and meters used in industrial production processes to automatically analyze and measure the composition and properties of substances. These instruments focus on automated analytical products required for combustion control, safe recovery of exhaust gases, process control, and quality monitoring. The data displayed by these instruments reflect the real-time conditions of the production process.
(1) When selecting process analytical instruments, it is essential to thoroughly understand the characteristics of the process medium in the object being analyzed, as well as the technical performance and other limitations of the selected instrument.
(2) A thorough assessment should be conducted on the instrument’s technical performance and economic benefits, ensuring that it can play its due role in guaranteeing product quality and production safety, enhancing economic efficiency, and reducing environmental pollution.
(3) The technical requirements for the analytical instruments and detectors selected shall be able to meet the operating temperature, pressure, and material properties of the medium being analyzed, particularly with regard to all background components and their respective concentrations.
(4) The instrument’s technical specifications—including selectivity, applicable range, accuracy, measurement range, minimum detection limit, and stability—must meet the requirements of the process flow and should feature reliable performance as well as simple operation and maintenance.
(5) Analytical instruments used in corrosive media or installed in flammable, explosive, or hazardous environments shall meet the relevant requirements or, after taking necessary measures, be able to meet the required usage conditions.
(6) The analytical instruments used for control systems must have a linear range and response time that meet the requirements of the control system.
Sampling and Preprocessing Device
(1) The samples taken from the sampling points shall be representative and should not cause any changes in composition or content after passing through the sampling system.
The sampling port should be located in a place easily accessible to maintenance personnel and should also take into account the temperature, pressure, and lag time of the sample.
The sampling port must not be located in low-velocity regions where the fluid flow is laminar, nor in the vortex zone or dead corners downstream of the throttling device.
(2) Gas samples should be kept free from liquid contamination, while liquid samples should be kept free from entrained gases. If the walls of the process pipeline tend to accumulate contaminants, the sampling probe should be inserted into the center of the pipeline. When the sample contains solid particles, a filter must be installed at the sampling point, and a back-blowing interface should also be provided.
(3) Based on the process conditions for sampling, the sampling system should be equipped with corresponding functions such as pressure reduction and flow stabilization, condensate discharge, overpressure relief, negative-pressure suction, fault alarm, and high-temperature resistance.
(4) During the sampling process, if condensates appear, it is essential to implement thermal insulation and heating measures. However, care must be taken to avoid overheating, which could alter the composition of the sample.
(5) The sampling pipeline should be as short as possible to minimize the lag time. Generally, the lag time of the sample delivery system should not exceed 60 seconds. The diameter of the sampling tube is typically φ6×1 mm; however, the maximum diameter of the sampling tube should not exceed φ14×2 mm.
(6) The material of the sampling tube is generally stainless steel. However, if the sample contains components that can corrode stainless steel tubes, other suitable materials such as polyvinyl chloride or polytetrafluoroethylene may be used. For non-corrosive dry samples, seamless steel pipes can also be employed. In addition, anti-blocking measures should be taken for the sample-leading pipelines.
(1) Pre-treatment devices typically include condensers, coolers, vaporizers, filters or purifiers, as well as treatment units employing chemical or physical methods to ensure the selectivity of analytical instruments. The specific configuration should be determined based on the characteristics of the sample and the technical requirements of the analytical instrument. Such devices are generally best supplied as complete sets by the analytical instrument manufacturer.
(2) After passing through the pretreatment device, the sample shall be clean, representative, free of harmful components, and meet the technical requirements of the analytical instrument’s detector for the sample.
(3) After passing through the pretreatment device, the concentration or composition of the analyte to be measured in the sample should remain unaffected.
Emission requirements for samples
(1) If the measured medium has recycling value, the sample should be considered for recovery.
(2) For multiple gas samples being vented, if the mixture of components is non-hazardous and the fluctuation in backpressure after mixing has little impact on the analytical instruments, the gases can first be routed to a gas collection manifold and then discharged into an appropriately elevated space. Otherwise, each gas should be vented separately.
(3) Toxic gases and liquid samples other than water may only be discharged if they meet the relevant hygiene standards.
(4) The materials of the components or pipelines in the pretreatment system shall not react with the sample, contaminate the sample, or adsorb any components from the sample.
Instrument Selection for Analyzing Components of Gas Mixtures
In a mixed gas with hydrogen content ranging from 0% to 100%, the thermal conductivities of the various components in the background gas are very close to each other, whereas their thermal conductivity differs significantly from that of hydrogen. Alternatively, when the composition of the background gas is relatively stable, it is advisable to use a thermal conductivity hydrogen analyzer. However, this type of analyzer is not suitable when the concentration of the component to be measured is low and the concentrations of the background gas components fluctuate considerably.
(1) In non-explosive hazardous areas where the hydrogen content is below 6%, the background gas may be air, nitrogen, argon, oxygen, or other gases. If the required analytical accuracy does not exceed ±0.1% and the response time is allowed to be up to 60 seconds, a suitable thermal conductivity hydrogen analyzer should be selected based on the specific composition of the background gas.
(2) In non-explosive hazardous areas, when the mixed gas is semi-water gas from a synthetic ammonia plant using coal as a feedstock—with a hydrogen content ranging from 35% to 75%—or when the mixed gas is fresh gas or recycle gas from a synthetic ammonia unit—with a hydrogen content ranging from 50% to 80%, if the required analytical accuracy does not exceed Class 2.5 and the response time is allowed to be up to 60 seconds, a hydrogen analyzer specially designed for small synthetic ammonia plants and large synthetic ammonia units should be selected.
(3) In areas with explosion hazards, when the hydrogen content in the gas mixture falls within the ranges of 40% to 80%, 80% to 100%, or 90% to 100%, an explosion-proof hydrogen analyzer should be used, or appropriate explosion-proof measures should be adopted.
(4) During argon production, the excess hydrogen content should be within the range of 0–3% or 0–2%. For hydrogen concentration in electrolytic oxygen, which should also be within the range of 0–2%, the measurement accuracy requirement is no higher than Class 5. In such cases, a suitable thermal conductivity hydrogen analyzer can be selected.
The selection of an oxygen analyzer should be based on the different background gas compositions and the specific oxygen concentration levels. For trace oxygen analysis, electrochemical or thermochimical oxygen analyzers should be used; for bulk oxygen analysis, magnetometric (including magnetic-flow, magneto-mechanical, and magnetic-pressure types) or zirconia-based oxygen analyzers are recommended.
(1) In the production process of hydrogen generation via electrolysis, when the oxygen content in the hydrogen gas at the outlet of the electrolyzer is between 0% and 1%, and the response time is allowed to be up to 90 seconds, a thermochemical oxygen analyzer should be selected. (When the oxygen content is between 0% and 0.5%, the instrument’s accuracy shall be Class 5; when the oxygen content is between 0% and 1%, its accuracy shall be Class 10.) If the analyzer is to be used in areas with explosion hazards, the manufacturer shall be required to provide explosion-proof instruments.
(2) In non-explosive environments where the oxygen content is below 21%, the background gas contains no corrosive gases, dust particles, or components with positive magnetic susceptibility such as nitric oxide and nitrogen dioxide, and where the background gas’s thermal conductivity, specific heat capacity, viscosity, and other properties remain relatively stable under operating conditions, if the response time requirement is up to 30 seconds and the analytical accuracy falls within the range of Class 2.5 to Class 10, a magnetic-induction (magnetic-flow principle) oxygen analyzer should be selected.
(3) In non-explosive hazardous areas, where the oxygen content ranges from 0% to 1%, 0% to 2.5%, 0% to 5%, 0% to 10%, 0% to 25%, and 0% to 100%, and where the background gas contains no corrosive gases, dust, or paramagnetic components such as nitric oxide and nitrogen dioxide, and where variations in the background gas’s thermal conductivity, specific heat capacity, viscosity, etc., are permissible, if the basic error requirement is no higher than Class 2 and the response time is allowed to be up to 7 seconds, a magneto-mechanical oxygen analyzer should be selected.
The gas sample pressure for this type of instrument can be either positive or negative.
(4) In non-explosive environments where the oxygen content ranges from 0% to 100%, if multi-range measurement is required or the initial measurement range is not zero, with a minimum range span of 0% to 1%, and if the measurement accuracy requirement is Class 1 and the response time is less than 2 seconds, a magnetic oxygen analyzer can be selected.
(5) In non-explosive hazardous areas, for flue gases from industrial boilers or other combustion systems containing oxygen levels ranging from 0% to 5% or from 0% to 10%, if the required analytical accuracy is no higher than Class 2 and the response time needs to be short, a zirconia-based oxygen analyzer can be selected. If the required analytical accuracy reaches Class 1 and the response time must be less than 2 seconds, a magnetic-pressure oxygen analyzer can be chosen.
(6) For measuring trace amounts of oxygen in high-purity gases such as hydrogen, nitrogen, and argon, as well as trace amounts of oxygen in other non-acidic gases, with measurement ranges of 0–10–50 ppm, 0–20–100 ppm, and 0–50–200 ppm, and requiring a measurement accuracy no greater than ±10% of full scale, an electrochemical trace oxygen analyzer should be selected.
Containing carbon monoxide or carbon dioxide gas
For the trace analysis of carbon monoxide and carbon dioxide in gases, conductivity-based or infrared absorption-based analyzers are typically used. For routine (major-component) analysis, infrared absorption-based analyzers are generally preferred. If the gas sample contains significant amounts of dust and moisture, these must be removed beforehand, or a thermal conductivity analyzer should be employed.
(1) For trace amounts of carbon monoxide and carbon dioxide in mixed gases or during ammonia synthesis, the background gas should be clean hydrogen, nitrogen, or high-purity nitrogen, oxygen, or argon, and must not contain hydrogen sulfide, unsaturated hydrocarbons, ammonia, or significant moisture. The temperature of the gas to be measured should be between 5°C and 40°C, and the pressure should exceed 0.5 MPa. In general, an infrared absorption-based trace gas analyzer is recommended. If high measurement accuracy is not required, a conductivity-based analyzer may be used instead.
The response time of the instrument depends on the time it takes for the gas sample to pass through the pre-processing device.
(2) The carbon monoxide or carbon dioxide content in the gas mixture ranges from 0% to 50% (expandable up to 0%–100%). The background gas must be dry, clean, free of dust and non-corrosive. When the required analytical accuracy is no higher than Class 5, an infrared gas analyzer is recommended. Its response time depends on the duration it takes for the gas sample to pass through the pre-processing device.
(3) In non-explosive environments, for boiler flue gases with a CO2 content ranging from 0% to 20% or kiln exhaust gases with a CO2 content ranging from 0% to 40%, the background gas may contain small amounts of carbon monoxide and sulfur dioxide, as well as relatively high levels of dust and moisture. When the required analytical accuracy does not exceed Class 2.5, a thermal conductivity-type CO2 analyzer can be used. Its response time depends on the duration it takes for the gas sample to pass through the pretreatment device.
Thermal conductivity analyzers require that the concentrations of the background gas components not fluctuate excessively.
Analysis of Other Components in the Mixed Gas
(1) To monitor the concentrations of methane, ammonia, sulfur dioxide, and hydrocarbon compounds in mixed gases, an infrared gas analyzer is recommended when the background gas is dry, clean, free of dust, and non-corrosive. Such analyzers can achieve measurement accuracy up to Class 1, and their response time depends on the duration it takes for the gas sample to pass through the pre-processing unit. They are also suitable for use in environments with explosion hazards.
(2) Nitrogen oxides, sulfur dioxide, hydrogen sulfide, chlorine gas, and other substances in the mixed gas or flue gas emissions shall be measured using a compact ultraviolet gas analyzer. The background gas must be clean, dry, and free of dust. The measurement accuracy requirement is no higher than Class 2. The response time depends on the duration it takes for the gas to pass through the pre-processing unit.
(3) Analysis of Sulfur Dioxide Content in the Mixture
① In non-explosive hazardous areas, when monitoring the concentration of sulfur dioxide in ambient air or the sulfur dioxide content in mixed gases within production processes over the ranges of 0–0.5, 0–1, 0–2, and 0–4 mg/m³, and where the background gas may contain small amounts of ozone, hydrocarbons, nitrogen dioxide, chlorine, etc., if the required measurement accuracy does not exceed Class 5 and the response time is allowed to be up to 5 minutes, a coulometric sulfur dioxide analyzer can be selected.
② In non-explosive hazardous areas, when the sulfur dioxide content in the mixed gas ranges from 0% to 15%, and the background gas contains acid mist (such as the inlet gas from the converter in a sulfuric acid production process), if the required measurement accuracy is no higher than Class 5 and the response time is allowed to be up to 1.5 minutes, a thermal conductivity-type sulfur dioxide analyzer can be selected.
③ In non-explosive hazardous areas, the mixed gas contains carbon monoxide, carbon dioxide, and small amounts of acid mist, moisture, mechanical impurities, and dust. If the sulfur dioxide content is less than 8%, and the required measurement accuracy does not exceed Class 10, with a response time allowed up to 3 minutes, an industrial polarographic sulfur dioxide analyzer can be selected.
(4) Analysis of the trace total sulfur content (organic sulfur and inorganic sulfur) in the gas mixture
For ammonia synthesis units that use natural gas as a feedstock, the trace sulfur content in the purified gas during hydrogenation and desulfurization must be no greater than 1 mg/l. Alternatively, the sulfur content in the gas pipelines of natural gas desulfurization plants and gas distribution stations must be below 30 mg/m³. The gas samples should be free of mechanical impurities, dust, moisture, and amine solutions. Moreover, the background hydrogen concentration in the gas sample should be less than 12.5%. When determining the total sulfur content in the gas sample, if the required measurement accuracy is no higher than Class 5 and the response time can be up to 2 minutes, it is advisable to use a coulometric microsulfur automatic gas analyzer. This instrument is suitable for use in potentially explosive environments.
Analysis of Multi-component Content in Mixed Gases
To analyze the content of a single component in a mixed gas or multiple components in multi-stream systems, with concentration ranges spanning from ppM levels to 100% by volume, an industrial gas chromatograph is recommended when analytical accuracy better than 1% is required. The response time depends on the sampling cycle and the gas pre-treatment time.
The commonly used detectors in industrial gas chromatographs are of two types: thermal conductivity detectors and hydrogen flame detectors. The former is suitable for measuring both organic and inorganic samples, while the latter is primarily used for detecting trace or semi-trace hydrocarbon compounds. It can also be used to measure trace amounts of carbon monoxide and carbon dioxide in hydrocarbon-containing organic compounds.
If a chromatograph is to be used for control systems or requires rapid acquisition of accurate analytical data, an intelligent, programmable chromatographic analyzer with integrated data processing capabilities should be selected.
The analysis cycle for a single sampling point in an industrial gas chromatograph typically ranges from 3 to 20 minutes, with one component sampled every 2 minutes. The number of sampling channels can range from 1 to 6, and the number of components analyzed at a single sampling point can range from 1 to 6 or from 1 to 40.
If the chromatograph is installed in an area with explosion hazards, an explosion-proof series chromatograph should be selected.
Analysis of Trace Moisture in Gases
For the measurement of trace amounts of water vapor—concentrations less than 100 ppm or 1,000 ppm—in gases such as air, inert gases, hydrocarbons, hydrogen, and other gases that do not damage the phosphorus pentoxide coating or the cell body and do not cause polymerization reactions on the electrodes—a phosphorus pentoxide electrolysis-based trace moisture analyzer should be selected. The sampling tube material must be dense with a smooth, clean inner surface; the pipeline should be short, and the sampling system must have excellent gas tightness.
Monitor or control the relative humidity of the air within the following ranges: 0–20%, 20–100%, and 50–100%. The ambient temperature should be between 10 and 40°C. The measurement accuracy shall be Class 3, and the response time shall be no more than 60 seconds. Under conditions where no condensation occurs in the gas phase, either a lithium chloride resistive hygrometer or a nickel-resistance thermometer-based psychrometer—or a platinum-resistance thermometer-based psychrometer—may be selected. Among these, both the lithium chloride resistive hygrometer and the nickel-resistance hygrometer must be equipped with indicating and adjusting instruments.
If the air temperature is below 10℃ or above 40℃, and the relative humidity exceeds 90%, a lithium chloride humidity transmitter or a on-off controller should be selected.
If the range of air humidity variation is relatively large and measurement accuracy of up to Grade 5 is acceptable, a humidity sensor based on bovine (or ovine) intestinal membrane can be selected. Its measurement range is 15% to 99%, with a sensitivity of 1% relative humidity and a hysteresis time no greater than 20 seconds.
Gas dew point measurement
(1) For detecting the dew point of compressed air and other non-corrosive dry gases within a dew point range of -60 to -40°C, with a required measurement accuracy better than ±1.5°C, an adiabatic expansion dew point meter can be selected.
(2) To determine the dew point of sulfuric acid in the flue gas from boilers burning sulfur-containing fuels, with dew point temperatures ranging from 0 to 180°C and from 180 to 460°C, and flue gas temperatures also ranging from 0 to 180°C and from 180 to 460°C, and with a required measurement error of less than ±1.5%, an acid dew point analyzer can be used.
Combustible Gas Calorific Value Detection
Continuously measure the calorific value of combustible gases such as city gas, natural gas, and biogas. The calorific value range is 700–15,000 kcal/m³ (2,900–62,800 kJ/m³), with a specific gravity between 0.4 and 1.3 kg/Nm³. The gas samples shall have an ash content of less than 5 mg/m³, a temperature below 50℃, and a pressure higher than 0.01–0.02 MPa. The response time must be no less than 45 seconds, and the accuracy must be better than Class 1.5. Either a combustion-based gas calorific value analyzer or a calorific index meter can be selected.
When selecting an analyzer, you should choose a calorific value analyzer with a suitable measurement range based on the calorific value and specific gravity ranges of the combustible gas. If the pressure of the gas being measured is less than 0.01 MPa, a sampling pump should be equipped. The instrument's response lag time primarily depends on the gas pre-treatment time.
Selection and Configuration of Combustible Gas Detectors
(1) A combustible gas detector is used to measure the concentration of various combustible gases in the air, provided that the concentration remains below the lower flammable limit of their vapor. The detector is required to trigger an alarm within a specified time frame when the concentration of the gas being measured reaches its explosive limit.
The indication range of the combustible gas detector should be from 0 to 100% LEL (Lower Explosive Limit), with a measurement accuracy of at least Class 5 and a response time of less than 30 seconds.
For a single flammable gas, a single-point alarm can be used; for multiple flammable gases or multi-point flammable gas detection, a multi-point combined alarm is recommended. The alarm should be installed on the instrument panel in the control room.
The lower and upper explosion limits for various combustible gases shall be based on the relevant provisions of the National Labor Bureau.
(2) Selection and Installation of Combustible Gas Detectors
The detectors used for combustible gas alarms mainly include semiconductor gas sensors and catalytic-beam (contact-combustion) sensors. The former are more sensitive to combustible gases but have lower quantitative accuracy, making them suitable for detecting the presence or absence of gas leaks. The latter offer high quantitative accuracy and excellent repeatability, making them ideal for measuring the concentrations of various combustible gases.
Detectors used in hazardous explosive environments must meet the explosion-proof rating of the installation location. For media that are corrosive, the parts of the detector that come into contact with the gas being measured must be treated with corrosion-resistant materials.
Combustible gas detectors should be installed near equipment that generates, processes, or consumes combustible gases, as well as in areas prone to combustible gas leaks, and in control rooms and on-site analytical instrument rooms where combustible gases may be produced and accumulated.
The installation location of the detector should be determined based on factors such as the production equipment, the leakage conditions at pipeline leak points, the specific gravity of the gas, as well as the site’s topography, prevailing wind direction, and air flow patterns.
The detector must not be installed in environments containing highly corrosive gases such as sulfur-containing and alkaline vapors.
(3) Detector Setup
Detectors are typically installed near equipment within buildings—such as compressors, pumps, reactors, and storage tanks—that are prone to leaks, as well as in areas where gases tend to accumulate. The detector configuration offers the following options for selection; however, adjustments can also be made based on actual conditions.
◆ Install more than one detector every 10 meters around equipment prone to leakage.
◆ For outdoor, open-air equipment, detectors should be installed around the equipment and in areas where gases tend to accumulate. In other locations, at least one detector should be installed every 20 meters.
◆Install detectors in production equipment with heat sources such as heating furnaces, as well as in areas where flammable substances tend to accumulate. Place at least one detector every 20 meters around the equipment.
◆ Install more than one detector around equipment used for filling toxic gases.
◆Install two or more detectors at the inlet and outlet ports of the liquefied petroleum gas storage tank area, as well as around these ports. Additionally, install one or more detectors on pipelines, equipment, and areas where gases tend to accumulate.
Instrument Selection for Analyzing Components of Liquid Phase Mixtures
Acid and Alkali Solution Analyzers
(1) Hydrogen ion concentration
Liquids contained in sinks, open channels, sealed pipes, or equipment—with hydrogen ion concentrations ranging from 1 to 12 pH—are typically measured at temperatures between 5 and 60°C (with a maximum of up to 90°C). If the solution does not contain any substances that could severely contaminate the glass electrode—such as oils or scale—then an industrial pH meter (glass-electrode type) can be used when measurement accuracy better than ±0.2 pH is not required.
For open containers such as sinks and open channels, submersible transmitters can be used. If the solution slightly contaminates the glass electrode, a submersible cleaning-type transmitter should be selected.
When the solution pressure inside the sealed pipeline is below 1 MPa, a flow-through transmitter can be selected. If the solution pressure in the pipeline is atmospheric and the glass electrode is slightly contaminated, a flow-through cleaning-type transmitter should be used.
For pH meters in which the transmitter and high-impedance transformer are installed separately, the connecting cable between them must be a shielded cable, and its length should generally not exceed 40 meters.
The immersion-type pH meter equipped with a solid calomel electrode eliminates the need for potassium chloride solution and integrates the transmitter with a high-impedance converter, offering enhanced resistance to interference. At the same time, the transmission distance can exceed 100 meters. The glass electrode is detachable, making it easy to clean and replace. This pH meter has a measurement range of 0 to 14 pH and an accuracy of ±0.2 pH.
If the liquid contains a high concentration of contaminant media, or in situations where glass electrodes are prone to breakage and the liquid does not contain oxidizing media, an antimony electrode pH meter is recommended. The measurement accuracy of this type of metal electrode is ±0.2 pH.
There are four types of cleaning-type transmitters, and the appropriate type should be selected based on the actual composition of the liquid being measured and the degree of electrode fouling.
(2) Concentration of hydrochloric acid solution
When measuring the regeneration of cation exchange resins using a dilute hydrochloric acid solution with a concentration ranging from 0% to 10%, or a dilute hydrochloric acid solution free from other salt impurities, at a temperature of 20 ± 10℃ and under a pressure below 1 MPa, and provided that the required measurement accuracy does not exceed Class 5, an electrical conductivity-based acidity meter or an electromagnetic-based concentration meter may be selected.
If the hydrochloric acid concentration exceeds 10%, but there is still a linear relationship between the concentration and its conductivity, and the solution does not contain other salt impurities whose conductivity varies significantly, an intelligent electromagnetic induction-based acid-base concentration meter with temperature compensation can be selected when the solution concentration is within the range of 26% to 36%. The temperature compensation range is 40 ± 10℃, and the accuracy class is 1.5.
(3) Sulfuric acid solution concentration
For sulfuric acid solutions produced in the sulfuric acid production process, or for similarly concentrated sulfuric acid solutions generated under other circumstances—provided that the solution contains no other acids or salts and its concentration and temperature remain within a certain range—electromagnetic or conductivity-based sulfuric acid concentration meters can be used.
For a 93% sulfuric acid solution, a density-type sulfuric acid concentration meter should be used.
(4) Sodium hydroxide solution concentration
For the regeneration of anion exchange resins, a sodium hydroxide solution with a concentration ranging from 0% to 8%, or a dilute sodium hydroxide solution free from other salt impurities, is used. The temperature should be between 20±10℃, and the pressure should not exceed 1 MPa. When the required measurement accuracy is no higher than Class 5, either an electromagnetic or a conductivity-based alkali concentration meter can be selected.
The electromagnetic concentration meter can also be used to measure potassium hydroxide solutions with concentrations ranging from 0.5% to 10%.
When measuring sodium hydroxide solutions with concentrations ranging from 30% to 35%, and when the solution temperature varies between 10°C and 80°C, an intelligent electromagnetic induction-based acid-base concentration meter with temperature compensation can be used. This meter has an accuracy class of 1.5. However, the solution being measured must not contain solids, air bubbles, or substances that tend to precipitate.
(5) Measurement of concentrations of various other solutions
When measuring the concentration of sodium hydroxide in waste alkaline black liquor, the concentration of sulfuric acid solution, the concentration of nitric acid in nitrification liquid, and the concentrations of refractive-index-based solutions such as tomato sauce, soy milk, syrup, brine, and cellulose acetate solution, if the concentration of a particular component in the solution has a unique linear relationship with the solution’s refractive index, and if the refractive index exceeds 1.3 while the solution contains no solid particles, then regardless of the nature or state of other components in the solution, a photoelectric refractometer can be used to determine the concentration of that specific component. This instrument features Class 1 measurement accuracy, allows for a maximum test solution pressure of 1 MPa, and operates at temperatures not exceeding 200℃.
Before selecting this type of instrument, you should first test the refractive indices of the solution to be measured (within its concentration range) at various concentrations in the laboratory, and only then can you determine whether it is suitable.
Measurement of Liquid Viscosity
The liquids to be measured include oils, paints, coatings, synthetic fibers, resins, rubber, plastics, medical gelatin, and more. If continuous viscosity measurement is required, various industrial-process viscometers should be selected according to the range of kinematic viscosities for different types of liquids as well as the instrument’s requirements for the temperature and pressure of the liquid being measured.
The ultrasonic viscometer can measure the viscosity of Newtonian fluids as well as non-Newtonian fluids, making it suitable for monitoring and controlling liquid viscosity in production processes.
Measurement of liquid specific gravity or density
(1) If changes in the specific gravity of the liquid being measured can cause variations in the ultrasonic reflection time, then the specific gravity of that liquid can be measured using an ultrasonic specific-gravity meter. The instrument’s measurement range can be individually calibrated according to specific requirements. The instrument requires an inlet liquid pressure between 0.05 and 0.6 MPa, and the temperature must not exceed 50℃. Measurement data from this type of instrument can achieve an accuracy of ±0.0005 g/cm³.
(2) If the liquid being measured contains few impurities or minimal bubbles, and if frequent manual analyses necessitate direct measurement of the liquid’s density under operating conditions in the pipeline, a vibrating-tube densitometer can be used. The measurement accuracy of this type of instrument can reach ±0.0005 g/cm³. However, vibrating tubes are difficult to manufacture and have stringent installation requirements. Moreover, if it is necessary to measure the density of a liquid at a specific temperature, an external thermostat must be added.
(3) For high-temperature, high-pressure, flammable/explosive, or highly corrosive media contained within sealed equipment—with densities ranging from 0 to 3 g/cm³—and pipe diameters between φ150 mm and 300 mm, if the required measurement accuracy is better than ±0.0005 g/cm³, a non-contact gamma-ray densitometer can be used. When explosion-proof requirements apply, an explosion-proof gamma-ray densitometer can be selected.
(1) Electrical conductivity
Distilled water, drinking water, boiler feedwater, pure water, and high-purity water—all with electrical conductivities ranging from 0.5 to 0.005 μS·cm⁻¹—require measurement accuracy below Class 3. In such cases, an industrial-grade conductivity meter for pure water can be selected. However, the water temperature should be maintained between 0°C and 60°C.
For industrial water or general boiler feedwater, with conductivity ranging from 0.1 to 1000 μS·cm⁻¹, and requiring measurement accuracy below Class 3, an industrial conductivity meter can be selected. However, the water temperature should be maintained between 0 and 60°C, and the pressure should be kept below 0.5 MPa.
For purified water treated with anion or cation exchange resins, a failure monitor for cation (anion) exchangers can also be used.
When selecting a conductivity meter, the cell constant of the transmitter should be chosen according to the conductivity range of the medium being measured. The distance between the transmitter and the converter generally should not exceed 20 meters.
(2) Salinometer
Continuously measure the salt content of steam condensate from thermal power boilers, with a measurement range from 0.1 to 0.4 mg/L to 2.0 to 4 mg/L (as NaCl). When measurement accuracy below Class 5 is required, an electrical conductivity-based salinity meter can be selected.
(3) Sodium ions
Determine the sodium ion concentration in boiler feedwater after treatment with a cation exchange resin. When the sodium ion concentration is between 2.3 and 2300 μg/L (PNa7 to PNa4), a sodium ion concentration meter can be used. The meter’s measurement accuracy is ±0.2 PNa. The pH of the water should be above 10, and the water temperature should be between 20 and 40°C. The distance between the transmitter and the converter generally should not exceed 40 meters.
(4) Silicate ions
After treatment with anion-exchange resin, the silicate content in boiler feedwater ranges from 0 to 100 μg/L, and the water temperature is between 15 and 40°C. The concentrations of interfering ions in the water shall comply with the following values:
Na+ < 500 μg/L, Ca++ < 200 μg/L, Zn++ < 200 μg/L, Cu++ < 200 μg/L, Fe++ < 200 μg/L, Fe+++ < 200 μg/L, Al+++ ≤ 15 μg/L.
When continuous monitoring is required due to frequent manual analyses, a silicate automatic analyzer can be selected. This instrument has a measurement accuracy of Class 5 and a response time of 15 minutes.
(5) Phosphate ion
To prevent boiler scaling, it is necessary to determine the phosphate concentration in the demineralized water when controlling the amount of phosphate added.
When the phosphate concentration is between 0 and 20 mg/L, the water temperature is between 15 and 45°C, and the concentrations of interfering ions in the water meet the following values:
Cl⁻ < 150 mg/L, Cu²⁺ < 1 mg/L, SiO₂⁻ < 50 mg/L, Fe³⁺ < 5 mg/L.
When continuous monitoring is required due to frequent manual analyses, an automatic phosphate analyzer can be selected. This instrument has a measurement accuracy of Grade 5 and a response time of 15 minutes.
(6) Turbidity
Continuously monitor the turbidity of water quality in tap water, industrial water, and river/lake water. The concentration of suspended solids ranges from 0 to 25 mg/L to 0 to 200 mg/L. The water should be free of strong acids, strong bases, and excessive bubbles, and its temperature should be maintained at 23°C. A turbidimeter can be selected for this purpose. Under rated conditions, the instrument exhibits a repeatability of 1% and a linear error of ±2%.
(7) Dissolved oxygen level in water
For boiler feedwater, the water temperature should be below 105℃, and the pressure should range between 0.1 and 0.5 MPa. The dissolved oxygen concentration in the water should be within the range of 0–20 μg/L, 0–50 μg/L, or 0–200 μg/L. When frequent manual analyses are required and continuous monitoring is needed, an electrochemical low-dissolved-oxygen analyzer can be selected. This instrument has an accuracy grade of 5 and a response time of 2 minutes.
The raw water or wastewater has a temperature ranging from 0 to 40°C and operates at atmospheric pressure. The dissolved oxygen concentration in the water is between 0 and 3 mg/L, 0 and 10 mg/L, 0 and 30 mg/L, or alternatively, the oxygen saturation level ranges from 0 to 30%, 0 to 100%, or 0 to 200%. When frequent manual analyses make continuous monitoring necessary, a dissolved oxygen analyzer can be selected. This instrument features a measurement accuracy of Class 5. It can be installed either in a flow-through configuration or as an immersion-type sensor. The distance between the measuring electrode and the transmitter should generally not exceed 10 meters.
(8) Comprehensive Water Quality Monitoring
To continuously and automatically monitor the water quality of rivers, industrial wastewater, and municipal water supplies in a comprehensive manner—or to receive alerts when water quality exceeds established standards—water quality monitors can be used. These instruments can comprehensively measure the pH value, dissolved oxygen, turbidity, electrical conductivity, and water temperature of water samples; however, they require the water temperature to be within the range of 5 to 40°C.
When continuous monitoring of various ions in industrial wastewater discharge is required, or when over-limit alarms are needed, an automated water quality monitoring system can be used for comprehensive monitoring.
Argon ions: 0.05–0.5–5 mg/L; chloride ions: 0.35–3.5–35 mg/L;
Cyanide ion: 0.1–1–10 mg/L; ammonium ion: 0.1–1–10 mg/L;
Nitrate ion: 1–10–100 mg/L.
Installation and Wiring of Analytical Instrument Detectors
Detector Installation Requirements
(1) The detector and the pre-processing device should be installed together and as close as possible to the sampling point. They generally should not be installed in the operating room.
(2) The analyzer should be located away from areas subject to strong vibrations and impacts, strong electromagnetic fields, and heat-generating equipment. It is also advisable to avoid, as much as possible, exposure to explosive gases and volatile, corrosive gases.
(3) The analyzer must not be directly exposed to sunlight and should be installed in locations where ambient temperature fluctuations are minimal and there is no risk of mechanical damage. In general, the surrounding air flow velocity should not exceed 3 m/s.
(4) Detectors installed directly on process pipelines must be equipped with protective covers or on-site analyzer cabinets.
(5) Whether or not to establish an automatic analyzer room shall be determined based on the type and quantity of analytical instruments used in the engineering design, as well as the environmental conditions of the installation site, and shall comply with the requirements of “Design Specifications for Automatic Analyzer Rooms” (HG 20516-92).
Individual non-explosion-proof instruments installed in outdoor hazardous areas where the likelihood of forming explosive mixtures is relatively low shall be housed within on-site analyzer enclosures. These analyzer enclosures shall meet the same requirements as those for automatic analyzer rooms, namely, they must comply with the "Design Specifications for Automatic Analyzer Rooms" (HG 20516-92).
Detector output signal line
(1) The cross-sectional area of the lead wires is typically between 1.0 mm² and 1.5 mm², and they must have excellent insulation and anti-interference performance. Alternatively, special lead wires may be used according to the requirements of the analytical instrument. When lead wires need to be routed through conduits, they should be installed inside steel pipes with good grounding.
(2) Signal cables must not be twisted together with power cables or routed through the same conduit. The routing of signal cables should, as far as possible, avoid running parallel to power cables and high-frequency signal cables.
(3) Instruments should be equipped with dedicated grounding wires that comply with the requirements of “Design Specifications for Instrument System Grounding” (HG 20513-92). The grounding wire must not be connected to the neutral conductor of the power supply.